| Classification ETIM 5 |
ETIM 5.0 Class-ID: EC000104 ETIM 5.0 Class-Description: Control cable |
| Classification ETIM 6 |
ETIM 6.0 Class-ID: EC000104 ETIM 6.0 Class-Description: Control cable |
| Core identification code |
Black with white numbers acc. to VDE 0293-334 |
| Conductor stranding |
Fine wire according to DIN EN 60228 (VDE 0295), class 5 / IEC 60228 class 5 |
| Torsion movement in WTG |
TW-0 & TW-1, refer to Appendix T0 |
| Minimum bending radius |
Occasional flexing: 20 x outer diameter. Fixed installation: 6 x outer diameter. |
| Nominal voltage |
U0/U: 300/500 V |
| Test voltage |
Core/core: 4000 V Core/screen: 2000 V. |
| Protective conductor |
G = with GN-YE protective conductor X = without protective conductor. |
| Temperature range |
Occasional flexing: -5°C to +70°C Fixed installation: -40°C to +80°C. |