Product

OLFLEX® CLASSIC 110

ÖLFLEX® CLASSIC 110 - PVC control cable, VDE registered, oil resistant and flexible for various applications, 300/500V, also for YSLY or YY.

  • CPR: Article number choice under www.lappkabel.com/cpr.

  • For nominal voltage U0/U: 450/750V or higher conductor cross-sections see ÖLFLEX® CLASSIC 100 450/750VVDE certificate of conformity with factory surveillance.

  • Product Description
  • Technical data
  • Note

Benefits


  • Wide choice of standardized lengths and individual cuts.

  • Very broad range, items with up to 100 conductors.

Application range


  • For fixed installation as well as occasional flexing at free, non-continuously recurring movement without tensile load.

  • Dry or damp rooms that are subject to medium mechanical loads.

  • Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG).

  • In power chains for a travelling distance up to 5 m and 0,2 ... 1 million bending cycles, for following dimensions: 0,5 to 2.5mm² and 2 to 7 conductors.

Product features


  • Flame-retardant according IEC 60332-1-2.

  • Good chemical resistance, see catalogue appendix T1.

  • Oil-resistant according to DIN EN 50290-2-22 (TM54).

Norm references / Approvals


  • VDE reg. no. 7030 for the following sizes:up to 2.5 mm²: 2 - 65 coresfrom 4 mm²: 2 - 7 coresfrom 25 mm²: 2 - 5 cores.

Product Make-up


  • Fine-wire strand made of bare copper wires.

  • PVC insulation LAPP P8/1.

  • Cores twisted in layers.

  • PVC outer sheath, grey (similar RAL 7001).

Technical Information


Classification ETIM 5 ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: Control cable
Classification ETIM 6 ETIM 6.0 Class-ID: EC000104
ETIM 6.0 Class-Description: Control cable
Core identification code Black with white numbers acc. to VDE 0293-334
Conductor stranding Fine wire according to DIN EN 60228 (VDE 0295), class 5 / IEC 60228 class 5
Torsion movement in WTG TW-0 & TW-1, refer to Appendix T0
Minimum bending radius Occasional flexing: 10 x outer diameter
In power chains: 15 x outer diameter.
Fixed installation: 4 x outer diameter.
Nominal voltage U0/U: 300/500 V
Test voltage 4000 V
Protective conductor G = with GN-YE protective conductor
X = without protective conductor.
Temperature range Occasional flexing: -15°C to +70°C
In power chains: -5°C to +70°C.
Fixed installation: -40°C to +80°C.
  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.

  • Copper price basis: EUR 150/100 kg. Refer to catalogue appendix T17 for the definition and calculation of copper-related surcharges.

  • Packaging size: coil ≤ 30 kg or ≤ 250 m, otherwise drum.

  • Please specify the preferred type of packaging (e.g. 1 x 500 m drum or 5 x 100 m coils).

  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.