Product

OLFLEX® CLASSIC 110 ORANGE

ÖLFLEX® CLASSIC 110 ORANGE - PVC control cable, flexible and numbered orange cores, especially for warning purposes and exempted circuits, also for YSLY or YY.

  • CPR: Article number choice under www.lappkabel.com/cpr.

  • For warning purposes and for exempted circuits according to EN 60204-1, e.g. circuits for maintenance or interlocking circuits.

  • Product Description
  • Technical data
  • Note

Benefits


  • Space-saving installation due to small cable diameters.

  • High electrical performance due to 4 kV test voltage.

Application range


  • According to EN 60204-1 (VDE 0113-1), conductors of control circuits that are supplied by an external power source and/or remain live when the main switch is deactivated must be orange.

  • Electrical lighting and socket circuits for maintenance or repair purposes.

  • Undervoltage protection circuits.

  • Interlocking control circuits.

  • Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG).

Product features


  • Flame-retardant according IEC 60332-1-2.

Norm references / Approvals


  • Based on IEC 60227-5 and EN 50525-2-51.

Product Make-up


  • Fine-wire strand made of bare copper wires.

  • PVC insulation LAPP P8/1.

  • Orange cores with black numbers.

  • Outer sheath: PVC, orange (similar to RAL 2003).

Technical Information


Classification ETIM 5 ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: Control cable
Classification ETIM 6 ETIM 6.0 Class-ID: EC000104
ETIM 6.0 Class-Description: Control cable
Core identification code Orange cores with black numbers.
Conductor stranding Fine wire according to VDE 0295,
class 5/IEC 60228 class 5.
Torsion movement in WTG TW-0 & TW-1, refer to Appendix T0
Minimum bending radius Occasional flexing: 15 x outer diameter
Fixed installation: 4 x outer diameter.
Nominal voltage U0/U: 300/500 V
Test voltage 4000 V
Protective conductor G = with GN-YE protective conductor
X = without protective conductor.
Temperature range Occasional flexing: -5°C to +70°C
Fixed installation: -40°C to +80°C.
  • Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon request.

  • Copper price basis: EUR 150/100 kg. Refer to catalogue appendix T17 for the definition and calculation of copper-related surcharges.

  • Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths.

  • Packaging size: coil ≤ 30 kg or ≤ 250 m, otherwise drum.

  • Please specify the preferred type of packaging (e.g. 1 x 500 m drum or 5 x 100 m coils).

  • Photographs and graphics are not to scale and do not represent detailed images of the respective products.